Output Volt Amp Capacity (VA) |
3000 |
Output kVA Capacity (kVA) |
3 |
Output Watt Capacity (Watts) |
2700 |
Output kW Capacity (kW) |
2.7 |
Output Capacity Details |
DE-RATING INFORMATION: Max output in Frequency Conversion mode is reduced to 1890 watts for 208/220/230/240V output voltages; Max output is reduced to 2160W at 200V output voltage in all operating modes OVERLOAD CAPACITY: Supports inverter operation up to 105% load continuously, 125% for 3 minutes, 150% for 30 seconds and >150% for 0.5 seconds before switching to BYPASS (when bypass input voltage and frequency are WITHIN bypass limits) or SHUTDOWN (when bypass input voltage or frequency are OUTSIDE bypass limits). |
Power Factor |
0.9 |
Crest Factor |
3:1 |
Nominal Output Voltage(s) Supported |
200V; 208V; 220V; 230V; 240V |
Nominal Voltage Details |
Nominal output voltage is user configured on first power-on |
Frequency Compatibility |
50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion |
Frequency Compatibility Details |
Output frequency matches input nominal on startup; Output capacity de-rates by 30% during frequency conversion operation |
Output Voltage Regulation (Line Mode) |
+/- 2% |
Output Voltage Regulation (Economy Line Mode) |
+/- 10% |
Output Voltage Regulation (Battery Mode) |
+/- 2% |
Output Receptacles |
(8) C13; (2) C19 |
Included Output Power Cables |
Includes 2 C13 to C14 and 1 C19 to C20 power cables |
Load Management Receptacles |
Two switchable 4 outlet load banks (3 C13 and 1 C19 per bank) |
Output AC Waveform (AC Mode) |
Pure Sine wave |
Output AC Waveform (Battery Mode) |
Pure Sine wave |