Output Volt Amp Capacity (VA) |
3000 |
Output kVA Capacity (kVA) |
3 |
Output Watt Capacity (Watts) |
2700 |
Output kW Capacity (kW) |
2.7 |
Output Capacity Details |
OVERLOAD CAPACITY: Supports inverter operation up to 105% load continuously, 125% load for 1 minute; 150% load for 30 seconds; Loads greater than 150% trigger immediate switchover to BYPASS (when input voltage and frequency are WITHIN bypass limits) or SHUTDOWN (when input voltage and frequency are OUTSIDE bypass limits) |
Power Factor |
0.9 |
Crest Factor |
3:1 |
Nominal Output Voltage(s) Supported |
220V; 230V; 240V |
Nominal Voltage Details |
230V default |
Frequency Compatibility |
50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion |
Frequency Compatibility Details |
ON LINE MODE: Output frequency is automatically configured to match nominal input frequency on startup; Output matches input frequency when +/-5Hz of nominal; Output is regulated to +/-0.05Hz when input frequency exceeds +/-5Hz of nominal. UPS switches to battery mode when input frequency is below 40Hz or above 70Hz. FREQUENCY CONVERSION MODE: Output is regulated to +/-0.05Hz of selected output frequency when input is 40 to 70Hz; UPS switches to battery mode when input frequency is below 40Hz or above 70Hz. BATTERY MODE: Output is regulated to +/-0.05Hz of selected nominal. |
Output Voltage Regulation (Line Mode) |
+/- 2% |
Output Voltage Regulation (Economy Line Mode) |
+/- 10% |
Output Voltage Regulation (Battery Mode) |
+/- 3% |
Output Receptacles |
(6) C13; (1) C19 |
Included Output Power Cables |
Includes three C13 to C14 power cables |
Output AC Waveform (AC Mode) |
Pure Sine wave |
Output AC Waveform (Battery Mode) |
Pure Sine wave |